ZW32-12 series owtdoor high-volage vacuum circuit breakers (hereinafitr referred to as " circuit breakers " are outdoor distribution swithgear with ratedvoltage of 12k V and three-phase AC of 50Hz.Cireuit breaker is mainmly used for opening and closing Load current, overload curent and short-eircuit currentin power lines have overload and short-circuit protection functions, meet the requirements of control and measurement. and can alsorealize remote controland monitoring functions, which are widely used in l is used for control and operation in distributio systems of substations and industrial and miningenterprises.and is especially suitable for places requiring frequcnt opcration.
Cireuit breakers meet technical standards such asGB1984-2003,DL/T402-2007 and IEC60056.
serial number | project | unit | data |
1 | Rated voltage | KV | 12 |
2 | Rated frequency | Hz | 50or60 |
3 | Current rating | A | 630 |
4 | Rated short-time interrupting current | KA | 20 |
5 | Rated peak withstand current | KA | 50 |
6 | Rated short-time withstand current | KA | 20 |
7 | Rated short-circuit closing current (peak) | KA | 50 |
8 | Mechanical life | times | 10000 |
9 | Rated number of short-circuit breaking current interruptions | times | 30 |
10 | Power frequency withstand voltage (1min) :(wet) (dry) interphase, ground/fracture | KV | 42/48 |
11 | Withstand voltage (peak) of lightning impulse interphase, to ground/fracture | KV | 75/78 |
12 | The secondary circuit has a power frequency withstand voltage of 1min | KV | 2 |