serial number | Projects | unit | data | ||||
1 | Rated voltage | KV | 12 | ||||
2 | Maximum operating voltage | KV | 12 | ||||
3 | Current rating | A | 630 1250 |
630,1250 1600,2000 2500,3150 |
1250,1600 2000,2500 3150,4000 |
||
4 | Rated short-circuit breaking current (rated thermal stability current - RMS) | KA | 20/25 | 31.5 | 40 | ||
5 | Rated short-circuit closing current (peak) | KA | 50/63 | 80 | 100 | ||
6 | Rated Peak Withstand Current (Rated Thermal Stability Current - RMS) | KA | 50/63 | 80 | 100 | ||
7 | 4S rated short-circuit withstand current | KA | 20/25 | 31.5 | 40 | ||
8 | Rated insulation level |
Working withstand voltage (before and after rated breaking) 1min power frequency withstand voltage | KV | To the ground 42 (fracture 48) | |||
Edge horizontal impulse withstand voltage (before and after rated breaking) / rated lightning impulse withstand voltage peak | To the ground 75 (fracture 85) | ||||||
9 | Rated thermal settling time | S | 4 | ||||
10 | Rated sequence of operations | Minutes - 0.3S-combines-180S-combines | |||||
11 | Mechanical life | times | 10000 | ||||
12 | Rated number of short-circuit interrupting currents | times | 50 | ||||
13 | Rated closing voltage of operating mechanism (DC) | V | AC,DC110,220 | ||||
14 | Ratde, Openin, Voltaji, Ben, Opelatin, Mechanism (DE) | V | AC,DC110,220 | ||||
15 | Contact opening distance | mm | 11±1 | ||||
16 | Overtravel (contact spring compression length) | mm | 3.5±0.5 | ||||
17 | Three-phase splitting, closing bounce time | Ms | ≤2 | ||||
18 | Contact closing bounce time | MS | ≤2 | ||||
19 | Average opening speed | m/s | 0.91.2 | ||||
20 | Average closing speed | m/s | 0.59.8 | ||||
21 | Opening time | at the highest operating voltage | S | ≤0.05 | |||
at the lowest operating voltage | ≤0.08 | ||||||
22 | Closing time | S | 0.1 | ||||
23 | The resistance of the main loop of each phase | μΩ | 630≤50 | 1250≤45 | |||
24 | Static and dynamic contacts allow for wear and accumulated thickness | mm | 3 |