FK (R) N12-12D/T type high voltage load switch is suitable for 12KV and below three-phase high voltage switching equipment, as transformers, cables, overhead lines and other power equipment control box protection; It is especially suitable for terminal substation and box-type substation of urban network and agricultural network. And suitable for ring network, double radiation power supply unit control and protection.
project | unit | FKN12-12D | FKRN12-12D | |||
Rated voltage | KV | 12 | 12 | |||
Rated frequency | Hz | 50 | 50 | |||
Current rating | A | 630 | 125 | |||
1min power frequency withstand voltage | To the ground, interphased | KV | 42 | 42 | ||
Rated insulation level | Isolate the fracture | KV | 48 | 48 | ||
Lightning impulse withstand voltage (peak) | To the ground, interphased | KV | 75 | 75 | ||
Isolate the fracture | KV | 85 | 85 | |||
Load switches | KA | 20 | / | |||
Grounding switch | KA | 20 | 20 | |||
Load switches | S | 4 | / | |||
Grounding switch | S | 2 | 2 | |||
Rated short-circuit closing current (peak) | KA | 50 | / | |||
Rated breaking current | Active load interrupting current | A | 630 | / | ||
Rated breaking current | Closed-loop interrupting current | A | 630 | / | ||
Rated breaking current | 5% active load interrupting current | A | 31.5 | / | ||
Rated breaking current | Cable charging current | A | 10 | - | ||
Rated breaking current | Interrupt no-load transformer capacity | KVA | 1250 | 1250 | ||
Rated short-circuit interrupting current limiting fuse | KA | / | 31.5 | |||
Rated transfer current | A | / | 1200 | |||
Mechanical life | times | 2000 | 2000 | |||
The impactor outputs energy | J | 1+0.5 |