project | unit | data | |||
Rated voltage | kV | 24 | |||
Rated frequency | Hz | 50/60 | |||
Rated insulation level | Rated short-time power frequency withstand voltage(1 min) | kV | 65 | ||
Rated lightning impulse withstand voltage | kV | 125 | |||
Rated short-circuit interrupting current | kA | 20 | 25 | 31.5 | |
Current rating | A | 6,301,250 | 63,012,501,600 | 1250,1600,2000,2500.3150 | |
Rated short-time withstand current(4s) | kA | 20 | 25 | 31.5 | |
Rated withstand current (peak) | kA | 50 | 63 | 80 | |
Rated short-circuit closing current (peak) | kA | 50 | 63 | 80 | |
Rated sequence of operations | O-0.3s-CO-180s-CO | ||||
Rated number of short-circuit current interruptions | times | 20 | |||
Rated short-circuit duration | S | 4 | |||
Mechanical life | times | 10000 | |||
The withstand voltage of the power frequency of the secondary circuit | V | 2000 | |||
Rated breaking current for a single capacitor bank | A | 630 | |||
Rated back-to-back capacitor bank interrupting current | A | 400 | |||
Dynamic and static contacts allow for wear and cumulative thickness | mm | 3 | |||
Opening time | ms | 20~60 | |||
Closing time | Ms | 25~70 | |||
Rated closing voltage/rated opening voltage | V | AC110/AC220/DC110/DC220 | |||
Rated voltage of energy storage motor | V | AC110/AC220/DC110/DC220 | |||
Motor power rating | W | 70 | |||
Energy storage time | S | ≤15 |